In short
- Outdoor lighting IP ratings run from IP44 splash to IP68, but the code describes a laboratory test on one sealed sample, not the wall, the cable or the joint.
- Most wet-luminaire failures begin at the cable entry, where a gland insert cut for 10 mm will not seal a 7 mm cable against a 12.5 litre jet.
- Specify the digit by location, the gland by measured cable diameter and 316 stainless by salt exposure, as three separate clauses in the RFQ.
An outdoor lighting IP rating is the two-digit code under IEC 60529 that states what a luminaire enclosure keeps out: the first digit covers solids such as dust, the second covers water from splashing to continuous immersion. It is a type test on a sample, not a statement about the wall, the cable or the joint made on site.
That distinction changes a purchase. A fitting can pass IP65 in a laboratory and still fill with water on a coastal terrace, because the test sample has its cable entry closed by the applicant, while the delivered unit carries a gland chosen by the factory and a cable chosen by the electrician. Two fittings with the same digits can behave differently within a season.
01The IP code describes a test, not a site
The first digit runs from 0 to 6, where 6 is dust-tight. The second describes the water and runs from 0 to 8. IP65 is dust-tight plus a jet from a 6.3 mm nozzle at 12.5 litres a minute for three minutes, not an upgrade of IP44 in every respect.
The report records whether water entered in a harmful quantity. It says nothing about the gasket after five summers, a coating on a cut edge, or a substituted gland.
| Code | Solids (first digit) | Water test (second digit) | Typical location |
|---|---|---|---|
| IP44 | Objects over 1 mm | Splashing water, 10 minutes | Sheltered soffit, covered balcony |
| IP54 | Dust-protected | Splashing water, 10 minutes | Porch under a deep eave |
| IP65 | Dust-tight | Jet, 6.3 mm nozzle, 12.5 L/min | Exposed wall, coastal façade |
| IP66 | Dust-tight | Powerful jet, 12.5 mm nozzle, 100 L/min | Deck edge, wash-down area |
| IP67 | Dust-tight | Immersion, 1 m for 30 minutes | Ground uplight, step light |
| IP68 | Dust-tight | Continuous immersion, by agreement | Pool basin, fountain, jet |
Test parameters to IEC 60529. An IP68 claim means nothing without the depth and duration in the report, which the standard leaves to agreement.
Decision rule: pick the second digit from the water the fitting will meet. A light under a 900 mm eave meets splash; a sea-facing balustrade meets driven rain and salt, and needs the material clause too.
02The cable entry is the joint that fails first
The entry fails first because the seal depends on a fit nobody checks. The first path is the gland itself: a 6–12 mm body holds a stepped insert cut back to the cable size, and an insert cut for 10 mm on a 7 mm cable is a nip rather than a compression. A 12.5 litre jet finds that in seconds.
The second path runs inside the cable: water reaching a stripped conductor travels between the strands and appears at the terminals while the gland is sound. A joint belongs above the water, with the cable entering from below.
The third path is the fixing: the sealing washer and locknut are the parts left in the box, and silicone bonds to the housing rather than the cable, hiding the gap.
- The insert cut to the measured cable diameter, not the nearest nominal size, with the range in millimetres.
- Entry on the underside or side face, never on the top face where water stands.
- A drip loop under the gland, cleated so wind cannot straighten it.
Decision rule: reject any detail where the cable enters the top face of a housing in the open. A top entry is a cup, and moving it costs a drawing revision.
Catalogue reference: decorative and custom lighting in the catalogue — models, dimensions and finishes for the directions discussed above.
03A sealed fitting still breathes
A fitting that passes IP65 cold can fill with water warm. At dusk the housing is warm; by midnight the air inside has cooled and contracted, and the seal that held a jet out now draws moist air in. It condenses on the diffuser with no route out.
Two details answer it. An ePTFE vent passes vapour and holds liquid water, so the housing breathes without admitting a jet. A gasket that keeps its elasticity does the rest: EPDM usually holds its elasticity longer than neoprene under UV.
The label carries the numbers: ta is the rated ambient, tc the maximum case temperature. A fitting marked ta 25 °C was tested at 25 °C, and a dark beam in summer sun is not that.
Decision rule: if the driver sits inside the housing, require a vent or a documented breather, and ta at or above the hottest air the site will see.
04Salt and UV choose the material, not the number
The code does not mention corrosion. Aluminium does not rust, having no iron in it, but it corrodes: the oxide layer is stable until chloride, a coating chip or a sheared edge gives the metal a start. Stainless is a family, not a grade: 304 is the common choice, and 316 adds 2–3% molybdenum to resist pitting.
Powder coating is a barrier, and barriers fail at edges. A 60 µm build is a common exterior planning reference, and the figure belongs on the order with the standard used to measure it; a drilled hole or a screw head that cuts the film is where the pit begins, and a steel fastener that pits leaves a rust stain down the coating.
UV is the other half. Polycarbonate diffusers yellow while acrylic and glass hold, and a hardened gasket is an open joint behind a label that still reads IP65. On a pergola, ISO 105-B02 lightfastness covers the fabric colour; the heat at the fabric is another clause.
Decision rule: in salt air, specify 316 for every fastener, gland nut and bracket, with salt-spray hours to ISO 9227 and a wash interval in the handover. A 316 fitting left unwashed still pits.
05Six locations, six different schedules
One product cannot answer every position, so write the schedule by location and then price it. The electrical designer sets the zone; local code governs.
| Location | Water it meets | Code and impact | Clause to add |
|---|---|---|---|
| Sheltered soffit | Splash, occasional wind-driven rain | IP44, IK05 | UV-stable diffuser if sun reaches it |
| Exposed wall or balustrade | Driven rain, salt spray | IP65, IK07 | 316 fixings, salt-spray report, wash interval |
| Step and low wall | Splash, grit, foot traffic | IP65, IK08 | Recessed bezel, no upward-facing joint |
| Ground uplight | Standing water, wheels | IP67, IK08; IK09 on a driveway | Clear drains, gravel layer, joint above water |
| Pergola beam | Rain above, driven rain under | IP65, IK07 | Anchor load to EN 1991-1-4, driver under cover |
| Pool basin | Immersion, chlorine | IP68 at the stated depth, 12 V SELV | 30 mA RCD, conduit and niche detail |
A starting schedule for a temperate coastal site; local code decides.
The pool row is not negotiable. A basin luminaire is 12 V extra-low voltage under IEC 60598-2-18, and circuits serving the pool zones need 30 mA additional protection under IEC 60364-7-702. The seal and the conduit decide whether the 12 V stays where it belongs.
Impact is the other omission. IK08 is 5 J, IK09 10 J, IK10 20 J. A terrace uplight takes a chair leg, a driveway uplight takes a wheel, and the test is on the glass, so a proud bezel changes what the fitting resists.
Decision rule: one line per location, and no substitution without a written check of code and impact class. The drive uplight and the basin light are not interchangeable.
06The driver decides the life, and it sits in the wrong place
The LED rarely fails. The driver does, and temperature sets its life. A rule of thumb is that an electrolytic capacitor loses half its life for every 10 °C rise in case temperature, so a driver sealed in a box at 70 °C will not reach its datasheet hours.
Remote in a ventilated enclosure is cooler and replaceable; integral is quicker and hotter. Ask for ta, tc and whether it can be changed without removing the fitting.
Voltage drop decides a 24 V scheme. On a 20 m two-core run at 4 A with 2.5 mm² copper the loop is 40 m, so the drop is about 1.1 V, or 4.7% of 24 V, at 0.0175 Ω·mm²/m. That dims the far end and pushes the driver towards its limit; 4 mm², or a shorter run, removes it.
Dimming adds a compatibility question: mains dimming depends on the driver matching the dimmer, 0–10 V needs its own pair, DALI needs commissioning. With 12 fittings behind one driver, minimum load bites.
Decision rule: put driver location, ta, tc, protocol and maximum load per driver in the RFQ, with the drop calculation for the longest run. A quote with a wattage and no driver is half a product.
07The RFQ page and the check on site
One page carries the order if it is written by location: code, material, entry, driver, reports. The sequence follows the order in which answers change a price.
- List the locations, each with a code, an impact class and a mounting height.
- Name the material for housing, bracket and every fastener, with the salt-spray report and its hours.
- Specify the entry: gland type, insert range in millimetres, entry face, drip loop and sheath type.
- State the driver location, ta, tc, dimming protocol and whether it is replaceable in place.
- Require the IP report page that names the sample, the cable diameter and the test parameters.
- Require the voltage drop calculation and the maximum number of fittings per driver.
- Attach the fixing detail, with the anchor load and the substrate it enters.
On arrival, open one carton per location, confirm the gland type and that the insert is cut for the cable you will use, check the gasket, and read ta and tc before anything goes up. A fitting that arrives with the wrong gland is a return; one sealed with silicone is a callback.
What your RFQ should state
- One schedule line per location, each with its IP code, IK class and mounting height.
- The IP report page that names the sample, the cable diameter used and the test parameters.
- Gland type and insert range in millimetres, the entry face, and the cable diameter it must seal.
- UV-rated cable, sheath type and conductor size, with a drip loop at every entry.
- Housing, bracket and fastener grades stated separately, with salt-spray hours to ISO 9227.
- Driver location, ta, tc, dimming protocol and whether it is replaceable in place.
- The voltage drop calculation for the longest run, and the maximum fittings per driver.
- For a pool basin, 12 V SELV to IEC 60598-2-18, 30 mA RCD and the depth stated for IP68.
Where this guidance stops
- This article describes codes and assemblies, not products. Two fittings with the same digits can differ in gasket compound, coating thickness and gland quality.
- An IP report is a type test on a sample. It cannot show a gasket in year five, and a photograph cannot show the cable entry at all.
- Local wiring codes differ on zones, RCD protection and who may connect a pool luminaire. IEC 60364-7-702, BS 7671 Section 702 and the US NEC do not say the same thing, and the destination's code governs.
- Salt-spray hours are not a service-life prediction. The result depends on the specimen, the scribe, the acceptance criterion and the maintenance regime.
- Foshan Supply coordinates sourcing, sampling and inspection. We do not test luminaires, issue IP or IK reports, design installations, or offer a universal warranty.
Questions buyers ask
Is IP65 enough for outdoor lighting?
For an exposed wall in a temperate climate, IP65 is a workable starting point: dust-tight, and tested against a 6.3 mm jet at 12.5 litres a minute for three minutes. It is not enough on its own. The material, gland, cable and driver location decide the outcome, and a coastal site also needs 316 fasteners and a wash interval.
What is the difference between IP65 and IP67?
Both are dust-tight. IP65 is tested against a water jet; IP67 is tested by immersion at 1 m for 30 minutes. A ground uplight standing in a puddle needs IP67. A wall light under an eave usually does not, and paying for immersion protection on that wall buys nothing unless the gland and cable are protected to the same level.
Why does water get into an IP65 light?
Almost always at the cable entry. An insert cut for a larger cable leaves an annular gap, a top entry collects water, or the sealing washer is missing where the gland passes through a thin wall. Water can also travel inside the cable between the strands and appear at the terminals while the gland itself is sound.
Do outdoor lights need RCD protection?
Usually, and the requirement comes from the wiring code of the destination rather than from the fitting. Under IEC 60364-7-702, circuits serving pool zones need 30 mA additional protection, and a luminaire inside the basin is limited to 12 V extra-low voltage under IEC 60598-2-18. Confirm the rule with the local electrical designer before first fix.
What does IK08 mean on a ground light?
IK08 is an impact rating under IEC 62262, tested at 5 J. IK09 is 10 J and IK10 is 20 J. A terrace uplight in a seating area is usually specified at IK08; a driveway or vehicle area at IK09 or above. The test applies to the glass, so a bezel standing proud of the paving changes what the fitting resists.
Should the LED driver be inside the fitting or remote?
Remote is easier to keep cool and easier to replace, which matters because the driver is the part that fails first. Integral is quicker to install and cheaper to detail, but it puts the driver in the hottest place in the assembly. Ask for ta and tc either way, so the choice is made on numbers rather than on a bracket.
Does IP68 mean a light can go in a swimming pool?
No. IP68 describes immersion under conditions agreed between buyer and maker, and says nothing about voltage. A pool luminaire must also be 12 V extra-low voltage to IEC 60598-2-18, installed in the niche and conduit the maker specifies, on a circuit with 30 mA additional protection. The IP number is one of three requirements, not a permission.
Sources
- IEC 60529 — Degrees of protection provided by enclosures (IP code) — International Electrotechnical Commission
- IEC 60598-1 — Luminaires: general requirements and tests — International Electrotechnical Commission
- IEC 60598-2-18 — Luminaires for swimming pools and similar applications — International Electrotechnical Commission
- IEC 62262 — Degrees of protection provided by enclosures against external mechanical impacts (IK code) — International Electrotechnical Commission
- IEC 60364-7-702 — Low-voltage electrical installations: swimming pools and fountains — International Electrotechnical Commission
- EN 1991-1-4 — Eurocode 1: actions on structures, wind actions — European Committee for Standardization
- ISO 105-B02 — Textiles: tests for colour fastness to artificial light — International Organization for Standardization
- EN 581 — Outdoor furniture: seating and tables for domestic, contract and public use — European Committee for Standardization
Pages related to this guide
How this guide was checked
- Written from the public catalogue, the standards and regulator pages listed under Sources, and the process records described on the services page.
- Catalogue references and model details were checked on 2026-11-05; 8 primary sources are linked above.
- No supplier paid for placement. No price on this page is an offer; ranges are planning references and must be confirmed in a quotation.
How these guides are researched and reviewed · Corrections policy