In short
- A U-value measures heat conducted through the window; SHGC measures the solar energy that ends up inside. A product can be good at one and poor at the other.
- Frame U-values run from 5.6–6.0 W/(m²·K) for plain aluminium to 1.6–2.2 for a 34 mm multi-chamber break, so the profile decides more of Uw than buyers expect.
- Uw is an area-weighted average under EN ISO 10077-1, so the same build-up declares 2.18 W/(m²·K) on a 1.5 m window and 1.70 on a 3 m one.
A U-value is the rate at which heat crosses one square metre of window for each kelvin of temperature difference across it, expressed in W/(m²·K). SHGC, the solar heat gain coefficient, is the fraction of incident solar energy that becomes heat inside the room, counted directly transmitted and absorbed then released inward, on a scale from 0 to 1.
Both appear on the same datasheet and answer different questions. One governs how fast a room loses heat on a cold night. The other governs how much heat the sun pushes in on a bright afternoon. A window specified on one number is specified for half its job.
01U-value measures heat leaving, SHGC measures heat arriving
A U-value is a rate in W/(m²·K); SHGC is a dimensionless ratio. That difference carries the whole argument: a rate always improves by getting smaller, while a ratio improves only where the building is cooling-dominated. In a house that needs winter heat, a high SHGC on a south window is a benefit.
| Attribute | U-value (Uw) | SHGC |
|---|---|---|
| What it measures | Heat conducted through glass, frame and edge, per m² per kelvin | Share of incident solar energy that becomes heat inside |
| Unit | W/(m²·K) | Dimensionless, 0 to 1 |
| Direction | Outward in cold weather, inward in hot weather | Inward only, and only while sun is on the glass |
| What lowers it | Wider break, low-e coating, argon fill, warm-edge spacer | Tinted or reflective glass, solar-control coating, external shading, less glass |
| What it costs | Money, and frame depth | Daylight, because visible transmittance usually falls with it |
| Reported under | EN 14351-1 declaration; NFRC label as U-factor | EN 14351-1 solar factor; NFRC label as SHGC |
The two columns are not comparable quantities and should never be added, averaged or traded one for one.
The buyer's mistake is rarely the definition. It is accepting one figure as proof of efficiency and never asking for the second. A supplier can quote a low Uw honestly and still deliver an opening that overheats a west-facing bedroom, because nothing in that number addresses solar gain.
02The frame is where an aluminium window loses heat fastest
Aluminium conducts heat at roughly 160 W/(m·K). Polyamide 66 with glass fibre, the strip that separates the inner and outer extrusion, conducts at about 0.3 W/(m·K). The ratio is about 530 to one, which is why a frame without a break behaves like a metal fin bonded to the glass.
The break is structural. The two extrusions are tied together by the strip, which carries wind load from sash to frame, so a wider strip means a deeper profile, heavier reinforcement and a larger mullion. Width is a design decision as much as a thermal one.
| Frame construction | Heat path | Indicative Uf |
|---|---|---|
| Plain aluminium, no break | Solid metal at about 160 W/(m·K) | 5.6–6.0 |
| 14.8 mm polyamide break | One strip at about 0.3 W/(m·K) | 3.0–3.5 |
| 24 mm break | Wider strip, usually two chambers | 2.0–2.8 |
| 34 mm multi-chamber | Several chambers, widest separation | 1.6–2.2 |
Planning references, not certified values. A declared Uf comes from a calculation or test on the actual profile, and two 24 mm frames can differ by half a unit through chamber geometry, wall thickness and gasket position.
Note what the table omits. The frame is a minority of the window area on most openings, so a deeper break does not halve the losses of the whole window. These are ranges for reading a quotation.
Catalogue reference: windows and exterior doors in the catalogue — models, dimensions and finishes for the directions discussed above.
03The declared Uw is an average, and the average depends on size
Uw is not measured on a window. Under EN ISO 10077-1 it is an area-weighted average of three paths, glass, frame and the linear bridge at the glass edge: Uw = (Ag × Ug + Af × Uf + lg × Ψg) / (Ag + Af), where Ag and Af are areas in m², lg is the glass perimeter in metres and Ψg is the edge transmittance in W/(m·K).
Take a 1,500 × 1,500 mm window with a 60 mm visible frame. Glass measures 1.904 m², frame 0.346 m², and the glass perimeter is 5.52 m, so the glass is 85% of the opening. The same construction at 3,000 × 3,000 mm is 92% glass, so the larger window declares the better Uw.
| Build-up | 0.9 × 0.9 m | 1.5 × 1.5 m | 3.0 × 3.0 m |
|---|---|---|---|
| Plain aluminium Uf 5.8, double glass Ug 1.2, Ψg 0.11 | 2.77 | 2.18 | 1.70 |
| 24 mm break Uf 2.4, double glass Ug 1.2, Ψg 0.05 | 1.69 | 1.51 | 1.36 |
| 34 mm break Uf 1.9, triple glass Ug 0.65, Ψg 0.05 | 1.15 | 0.96 | 0.81 |
Our arithmetic from the EN ISO 10077-1 relationship, not a test result. Ug and Uf sit mid-range; substitute the supplier's declared values and the ranking holds while the figures move.
This is the trap in a mixed schedule. A factory calculates or tests a sample, declares the result, and the buyer applies it to forty openings of different sizes. A 900 mm bathroom window in the same system is a measurably worse product than the 3 m slider behind the headline figure, and the shortfall shows as condensation in the first cold week.
04A low SHGC buys cooling and spends daylight
Solar gain is arithmetic a buyer can do without software. Through an area A with coefficient S under irradiance I, the gain is A × S × I; conduction through the same window is A × Uw × ΔT. The two are equal when S × I = Uw × ΔT, and that crossover is the whole argument.
Put the 1.5 m window against a 10 K difference: 2.18 × 10 gives 21.8 W/m². At an SHGC of 0.6 the sun need only deliver about 36 W/m² to match the heat loss; at 0.3 it needs about 73 W/m². A sunlit west facade delivers far more than that for hours, so solar gain, not conduction, sets the cooling load.
The cost is daylight. The NFRC label reports visible transmittance next to U-factor and SHGC, and a coating that rejects solar energy generally rejects light with it. Darkening the glass trades a cooling problem for a lighting one, which is why external shading, a deep reveal or a smaller aperture often answer the brief better.
Read the document before comparing the figure. EN 14351-1 declares a solar factor, g, while the NFRC label declares SHGC. Both describe the share of solar energy that becomes heat inside, but different procedures and spectra produce them. Copying a g-value into a document that asks for SHGC is a substitution a reviewer will catch.
05A fixing through the break cancels the frame's number
The declared Uw assumes an uninterrupted profile. A stainless hinge leaf, a fixing screw or a bracket that crosses the break hands heat a metal path from the warm extrusion to the cold one, and the frame behaves locally like plain aluminium. The calculation cannot see it and the label does not report it.
The second failure is quieter. A warm-edge spacer cuts the linear transmittance at the glass edge, Ψg, from roughly 0.10–0.12 to 0.04–0.06 W/(m·K). On the 1.5 m window above, that change alone moves Uw from 1.11 to 0.96 W/(m²·K). It is a small component, it is invisible after glazing, and it is the first item substituted when one quote comes in below another.
Test the detail rather than the claim. On a cold morning an infrared thermometer run down the frame shows where the break is interrupted. Condensation on the inner face is not always humidity; it is often a bridge, usually where something is fixed.
06The label reports a product, not an opening
EN 14351-1 is the harmonised product standard for windows and doors in the European Union, and the basis on which a manufacturer declares thermal transmittance, solar factor and the classes below, with CE marking against the Construction Products Regulation. In the United States the NFRC route reports U-factor, SHGC, visible transmittance and air leakage on a label, and AAMA 1503 covers the thermal transmittance test for frames.
| Standard | What it classifies | Class range |
|---|---|---|
| EN 12207 | Air permeability | 1 to 4 |
| EN 12208 | Watertightness | 1 to 9A |
| EN 12210 | Wind resistance | 1 to 5 |
None of these classes is an energy rating. A window can reach class 4 on air, 9A on water and 5 on wind and still perform poorly on heat loss or solar gain.
A CE mark declares that the product conforms to the harmonised standard as declared. It does not certify the installed opening, the reveal, the sealant or the wall junction. A test on one size does not certify another.
07Specify both numbers against a compass direction
A schedule line reading Uw 1.4, SHGC 0.3 is not a specification until it carries a size and an orientation. The sequence below turns the two numbers into something a factory can price and a site can check.
- List every opening by orientation, size and glazed area, in groups rather than as one system.
- State the Uw target per group with the size it applies to, and require a calculation for the smallest and largest in each.
- Set a maximum SHGC on east and west glazing, where low sun is hardest to shade, and state where winter gain is wanted.
- Set a minimum visible transmittance so a solar-control target cannot be met by darkening the glass.
- Name the spacer type and the maximum glass-edge transmittance, and forbid substitution without approval.
- Require the fixing and hinge detail by drawing, with the isolation method shown wherever it crosses the break.
- Name the standard route for each declaration, EN 14351-1 or NFRC 100 and 200, and say which governs.
It makes two quotes comparable, because each has to state the size, the build-up, the class, the spacer, the fixing detail and the standard.
What your RFQ should state
- Uw for each size group to EN ISO 10077-1, with the frame, glass and edge values behind it.
- Solar factor to EN 14351-1 or SHGC to NFRC 200, plus visible transmittance, for the glazing supplied.
- Orientation limits: a maximum SHGC on east and west glazing, and a stated position on winter gain.
- Spacer type and its maximum glass-edge transmittance, with substitution subject to written approval.
- The fixing, hinge and bracket detail by drawing, showing non-metallic isolation at every crossing.
- Air, water and wind classes to EN 12207, EN 12208 and EN 12210, stated apart from the energy figures.
- The declaration of performance and label, naming the same profile and glazing build-up as the order.
Where this guidance stops
- Frame U-values here are indicative ranges for reading a quote, not certified values; only the supplier's calculation or test covers the product supplied.
- The Uw figures are our arithmetic from EN ISO 10077-1 with a 60 mm visible frame and mid-range values; your sizes will give different answers.
- This article does not model a building. Overheating and daylight depend on shading, orientation, occupancy and climate, which belong in an energy model.
- A photograph cannot show the spacer, the isolation washers or the chamber geometry inside a profile; those need a drawing and a declaration.
- Foshan Supply coordinates sourcing, specification review and inspection. We do not issue test reports, certify products or offer a universal warranty; the supplier's declared data and the inspection scope govern.
Questions buyers ask
Is a lower U-value always better on a window?
For heat loss, yes: a lower U-value means less conducted heat and a warmer inner frame surface. It is not the whole picture. A window with an excellent U-value and an unmanaged SHGC can still overheat a west-facing room, and the number says nothing about daylight or air leakage.
Should SHGC be high or low in a cold climate?
It depends on room and orientation. On a south window in a heating-dominated climate, a higher SHGC admits free winter heat, and suppressing it raises the heating bill. On east and west glazing, low sun arrives at a shallow angle and is hard to shade, so a lower SHGC is usually safer.
Why does my window's U-value differ from the brochure?
Because Uw is an area-weighted average and the brochure figure belongs to one size. The frame is the weaker path, so a small opening with a large frame share declares a worse Uw than a large slider of the same construction. Our example runs from 1.70 W/(m²·K) at 3 m to 2.18 at 1.5 m.
What does a warm-edge spacer actually change?
It reduces the linear transmittance at the glass edge, from roughly 0.10–0.12 to 0.04–0.06 W/(m·K). In the 1.5 m example that alone moves Uw from 1.11 to 0.96 W/(m²·K). It also lifts the inner glass-edge temperature, where condensation starts on a cold morning.
Does a CE mark prove the window meets its U-value?
No. A CE mark declares conformity with the harmonised standard as declared by the manufacturer, for the product as placed on the market. It does not test your opening, and it does not cover the installation, reveal, sealant or wall junction. Read the declaration of performance and check it names your build-up.
Can I compare a European g-value with an NFRC SHGC?
Not directly. Both express the share of solar energy that becomes heat inside, but different procedures and different solar spectra produce them. If your specification names one, ask for that one. Pasting a g-value into an NFRC schedule, or the reverse, creates a substitution a reviewer will reject.
What single question reveals a weak window quote?
Ask for the Uw of the smallest opening on the schedule, with the frame, glass and edge values behind it. A supplier with a real calculation answers in a day. A supplier working from a brochure will offer the system figure, then the reference size, and neither is the window you are buying.
Sources
- ISO 10077-1:2017 — Thermal performance of windows, doors and shutters: calculation of thermal transmittance, Part 1: General — International Organization for Standardization
- EN 14351-1 — Windows and doors: product standard, performance characteristics — European Committee for Standardization
- NFRC ratings and the energy performance label: U-factor, SHGC, visible transmittance and air leakage — National Fenestration Rating Council
- AAMA 1503 — Voluntary test method for thermal transmittance of fenestration frames — American Architectural Manufacturers Association
- CE marking: the rules for placing products on the EU market — European Commission
- Construction Products Regulation (EU) No 305/2011 — European Commission
- ISO 9050:2003 — Glass in building: determination of light transmittance, solar direct transmittance and total solar energy transmittance — International Organization for Standardization
Pages related to this guide
How this guide was checked